MSE 8000 safety and compliance
information
On this page:
Safety information symbols
 |
A note provides information
which you should consider. |
 |
A caution carries information
about procedures or events which if not considered may
cause damage to the data or hardware of your
system. |
 |
A warning carries information
about procedures which must be followed to reduce the
risk of electric shock and danger to personal
health. |
 |
This symbol, where it appears,
indicates that there might be a hazard due to moving
parts. |
 |
The book symbol, where it
appears on the unit, indicates that you must read the
manual (this safety information and the Getting Started
Guide that accompanied the
unit). |
Safety precautions and general
hazards
The following general safety precautions must be observed
during all phases of operation, service and repair of this
equipment. Failure to comply with these precautions or with
specific warnings elsewhere in this manual violates safety
standards of design, manufacture and intended use of the
equipment. Codian assumes no liability for the customer's
failure to comply with these requirements.
 |
If the MSE 8000 is installed in
a closed or multi-unit rack assembly, the ambient
temperature may be greater than the room ambient
temperature, therefore consideration should be given to
installing the MSE 8000 in an environment compatible
with the maximum rated ambient temperature specified in
the Operating
Environment section of this
information. |
 |
The installation of the MSE 8000
in a rack should be such that the amount of air flow
required for safe operation is not
compromised. |
 |
Mounting of the MSE 8000 in a
rack should be such that a hazardous condition is not
achieved due to uneven mechanical
loading. |
 |
The MSE 8000 must be installed
in a restricted location as defined by EN, IEC and
UL60950. This is defined as an area intended for
qualified or trained personnel only with access
controlled by a locking mechanism such as a
key. |
 |
The MSE 8000 when fully loaded
with blades can exceed 100kg (220 pounds) in weight. The
MSE 8000 weighs approximately 50kg (110 pounds) when
empty of blades and fan trays. Two people using an
appropriate lifting device are required to install the
MSE 8000 system or remove it from a rack
safely. |
 |
All operations for the
installation can only be performed within a restricted
location by trained service personal. The MSE 8000 has
no user installed parts. |
 |
The MSE 8000 must be placed in
the lowest available place within a rack to provide
stability. If the rack provides stabilizers they must be
used during installation. |
 |
The MSE 8000 uses front-to-rear
cooling fans. To ensure adequate cooling, allow a
minimum of 91.4cm (36 inches) in front and at the rear
of the MSE 8000 system. Allow the same distance for
installation and servicing. Do not block the fan intake
or outlet. Ensure that the fan intake is not placed
inline with the outlet from any other fan or convection
cooled device. |
 |
Ensure that the rack has been
installed in the building in accordance with the
manufacturer's instructions and that it is strong enough
to accommodate the weight of the MSE 8000 and any other
units placed within it. |
 |
Before un-installing the unit
from the rack, all blades must be removed from the
chassis and all power connections must be removed from
the MSE 8000. |
 |
You must install either a blade
or a blanking blade in each of the ten slots in the
chassis. |
 |
Each power cable is required to
have its own circuit breaker. |
 |
All circuit breakers must be in
the OFF position before installing or removing the power
connections. |
 |
For power redundancy, each power
feed should be powered from a separate power
source. |
 |
Only specified hot swap
operations are allowed with the power connected. For all
other actions, you must either disconnect the power or
have the circuit breakers in the off position. All
circuit breakers must be OFF to remove power from the
MSE 8000. |
 |
Warning! Hazardous moving
parts. Keep fingers and other body parts
away. |
 |
The MSE 8000 is capable of
accepting -40.5V DC to -72V DC in abnormal conditions.
It is highly recommended that only -48V DC to -60V
DC is used. |
 |
Any DC power cable supplied with
an AC power supply unit for the MSE 8000 is considered
an internal cable to the MSE 8000
system. |
 |
The MSE 8000 powering scheme
does not require a reference to earth from the negative
or return lines. The conditions for powering the MSE
8000 are such that the negative terminal must have a
more negative voltage than the return terminal, and that
power inputs A and B must each provide identical
powering schemes. |
 |
Fuses on the system blades and
fan trays are not operator or service personnel
replaceable parts. |
Servicing the MSE 8000
Fuse identification is by the following markings on the
system blades and fan trays. All MSE 8000 fuses are of
identical type, Rated voltage 250 VAC, Rated Current 6.3A,
Breaking Capacity 1500 A, Characteristic Quick
Acting.
Blade fuses in negative and return lines in
both Sources A and B indicated by J7, J8, J9 and J10 located
on the power boards on each of the blades.
Fan tray
fuses in negative and return lines in both Sources A and B
indicated by J9, J10, J11 and J12 located on the power boards
on each of the fan trays.
Note that the MSE 8000 fuses are not customer or service
personnel replaceable parts.
The safety precautions listed below represent warnings of
certain dangers of which Codian is aware. You, as the user of
the product, should note these warnings and all other safety
precautions necessary for the safe operation of the equipment
in your operating environment.
Do not service or adjust alone
 |
Do not attempt internal service
or adjustment unless another person, capable of
rendering first aid and resuscitation, is
present. |
Operating guidelines
- Risk of electrical shock if opened. Never operate with
cover removed
- No user serviceable parts
- Only trained and qualified personnel should install or
replace this equipment
- Rack-mount following the instructions in the MSE 8000
Getting Started Guide that accompanied the unit
Safety warnings
- Only trained and qualified personnel should be allowed
to install or replace this equipment
- Read the installation instructions in the MSE 8000
Getting Started Guide that accompanied the unit before you
connect the system to its power source
- The MSE 8000 does not contain any replaceable batteries
and the internal batteries are designed to last the lifetime
of the system
 |
Never defeat the earth (ground)
conductor or operate the equipment in the absence of a
suitably installed earth conductor. Contact the
appropriate electrical inspection authority or an
electrician if you are uncertain that suitable earthing
is available. |
- Ultimate disposal of this product should be handled
according to all national laws and regulations
 |
Do not operate the unit with the
cover removed. Operating the unit without the cover in
place will invalidate the safety approvals and pose a
risk of fire and electrical
hazards. |
 |
Do not work on the DC power
lines while the system is connected to
power. |
 |
Do not work on the
system or connect or disconnect cables during periods of
lightning activity. |
 |
To avoid electric
shock, do not connect safety extra-low voltage (SELV)
circuits to telephone-network voltage (TNV) circuits.
LAN ports contain SELV circuits, and WAN ports contain
TNV circuits. Some LAN and WAN ports both use RJ-45
connectors. Use caution when connecting
cables. |
- The console, Ethernet and ISDN ports on the ISDN module
are SELV interfaces. ISDN lines where they enter the
building are usually classified as TNV. These lines should
never be connected directly to the ISDN module. Use an
isolating device such as a Network Termination Unit (NTU) or
Channel Service Unit (CSU) between off-premise ISDN lines
and the ports on the ISDN module
 |
This equipment is to
be installed and maintained by service personnel only as
defined by AS/NZS 3260 Clause 1.2.14.3 Service
Personnel. |
 |
To prevent bodily injury when
mounting or servicing this unit in a rack, you must take
special precautions to ensure that the system remains
stable. The following guidelines are provided to ensure
your safety:
- This unit should be mounted
at the bottom of the rack if it is the only unit in
the rack
- When mounting this unit in a
partially filled rack, load the rack from the bottom
to the top with the heaviest component at the bottom
of the rack
- If the rack is provided with
stabilizing devices, install the stabilizers before
mounting or servicing the unit in the rack
|
Safety requirements
For protection, observe the following safety precautions
when setting up the equipment:
- Follow all cautions, warnings, and instructions marked
on the equipment
- Ensure that the voltages and frequency rating of your
power source match the voltage and frequency inscribed on
electrical rating label attached to the equipment
- Never push objects of any kind through openings in the
equipment. They may touch dangerous voltage points or short
components, resulting in fire, electric shock, or damage to
your equipment
- Refer servicing of equipment to qualified personnel
Lifting
 |
Owing to the weight
of the system, do not attempt to install it in or remove
it from a rack without an appropriate lifting device.
|
Modifications to equipment
 |
Because of the
danger of introducing additional hazards and/or the
possibility of compromising emissions compliance, do not
install substitute parts or perform any unauthorized
modification of the equipment. Contact your local
support organization for service and repair to ensure
that safety features are maintained.
Codian is not responsible for
regulatory compliance of a modified Codian
product. |
SELV compliance
The safety status of I/O connections complies with SELV
requirements.
Power connection
The disconnect devices for servicing are defined as the
circuit breakers in all power supply conductors.
 |
The MSE 8000 must be
installed in a restricted access location. The IEC, EN
and UL 60950 define a restricted access location as an
area intended for qualified or trained personnel only
and having access controlled by a locking mechanism,
such as a key lock or an access card
system. |
 |
The MSE 8000 is
shipped with protective earthing terminals on the rear
of the chassis. To reduce the risk of electric shock,
always ensure that these terminals are connected to
earth within the installation. |
Connect a protective earth cable to the protective earth
terminals on the rear of the chassis. The protective earth
terminals are marked with the earth symbol. Connect the other
end of this earth cable to a true earth or the same earth as
other equipment within the restricted location. The protective
earth connection must comply with applicable national, local,
and site regulations.
 |
The earth symbol
indicates the location on the unit of the protective
earthing terminals. |
DC connections to the MSE 8000
This section describes connecting a DC power feed to the
MSE 8000.
Before attempting to connect power to the MSE 8000, make
sure of the following conditions:
- The chassis is connected to protective earth as
described above
- There is a circuit breaker in each power supply
conductor that is correctly rated to comply with local and
international regulations
- All circuit breakers are in the OFF or disconnected
position
- The DC power lines are capable of taking the maximum
current and voltage for the MSE 8000 system and only double
hole lugs will be used to connect the DC cables to the
terminals of the MSE 8000
- The DC power supply gives the correct DC voltage -48V DC
to -60V DC
- The two fan trays are installed
- Every slot in the chassis has either a blade or blanking
blade installed
To connect DC power cables to the MSE 8000:
- Using a TORX T20 screwdriver, remove the four screws
that secure the transparent cover at the rear of the
chassis; remove the transparent cover.
- Connect the negative and return power cables to the MSE
8000 DC terminals.
 |
The DC terminals of
the MSE 8000 accept double hole lug connectors on a 3/4
inch (19.1mm) spacing. The diameter of the terminals
is 1/4 inch (6.4mm). |
- Tighten all nuts to a torque of 4 Nm (35 inch pounds).
- Connect the DC cables to the circuit breakers according
to the manufacturer's instructions.
- Ensure all the power connection terminals are connected
at the correct polarity and torque.
- Refit the transparent cover before switching on the
power supply or engaging the circuit breakers in the ON
position.
 |
To comply with the
NEC regulations in North America, 90°C 2 AWG copper
cables must be used. Where other international
regulations apply, 4 AWG or 25mm2 copper cables can be
used. |
 |
The circuit breakers
are the only means of disconnecting power from the MSE
8000. |
Technical
specifications
Power requirements
Table 1: MSE 8000 ratings
|
Rating |
Value |
|
Nominal voltage |
-48V DC to -60V DC |
|
Maximum input current per cable |
85A at -48V DC |
|
Circuit breaker (NEC requirement) |
125A |
|
Circuit breaker (other than NEC) |
100A |
Operating environment
The MSE 8000 is for indoor controlled environment use
only.
The MSE 8000 must only be used within the following
environmental conditions:
Table 2: Operating environment
|
Environment |
Temperature |
Humidity |
|
Operating environment |
0°C to 35°C |
10% to 95% (non-condensing) |
|
Non-operating environment |
-10°C to 60°C |
10% to 95% (non-condensing) |
|
Optimum operating environment |
21°C to 23°C |
45% to 50% (non
condensing) |
Anti-static
precautions
 |
Wear an anti-static
wrist strap and use an ESD-protected mat when handling
components. |
When servicing or removing components or connections, first
attach an anti-static wrist strap with a banana plug
connection to the ESD grounding socket provided on the top
front of the unit.
The ESD grounding socket is marked with the following
symbol:
Figure 1: ESD grounding socket symbol
Compliance
information
USA — Electromagnetic Compatibility Information
System Classes
In the United States, the Federal Communications Commission
(FCC) governs the levels of electromagnetic emissions from a
digital device. Electromagnetic emissions can interfere with
radio and television transmission. To reduce the risk of
harmful interference, the FCC has established requirements for
manufacturers of digital devices.
FCC statement
FCC Class A
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this device
must accept any interference received, including interference
that may cause undesired operation.
European Union Notice
COMPLIANCE IDENTIFICATION: DT1AD
The Declaration of Conformity is available on request.
Products with the CE marking comply with the protection
requirements of the following EU Directives:
- EMC Directive 89/336/EEC, as amended by 93/68/EEC, by
application of the following harmonized standards:
- EN55022:1998—Electromagnetic Interference
- EN50024:1998—Electromagnetic Immunity
 |
This is a Class A
product. In a domestic environment, this product may
cause radio interference in which case the user may be
required to take adequate measures to correct this
interference. |
- Low Voltage Directive 73/23/EEC, as amended by
93/68/EEC, by application of the following harmonized
standard:
- EN60950: 2001, Safety of Information Technology
Equipment.
To ensure compliance
To ensure compliance, the system must be reliably connected
to earth using the unit's earth terminals.
Canada — Electromagnetic Compatibility Information
Communications Canada (i.e., the Department of
Communications) regulates digital devices similar to the FCC
in the United States. Every product should be labeled or
provided with documentation that states the class of the
product. The DOC defines the environment in which a digital
device should be used as the FCC does. Products labeled DOC
Class A are for an industrial or a commercial area.
The MSE 8000 is DOC Class A and should not be used in a
residential area. An end-user in Canada is responsible for
ensuring that his system is suitable for its environment as
stated in the above paragraph.
ICES-003 Class A Notice
This Class A digital apparatus complies with Canadian
ICES-003.
Finland
Laite on liitettävä suojamaadoitus-koskettimilla
varustettum pistorasiaan.
Norway
Apparatet må tilkoples jordet stikkontakt.
Sweden
Apparaten skall anslutas till jordat uttag.
WEEE information
For UK customers only, the EEE producer registration number
is WEE/BA0058TS. For all other European countries please refer
to your distributor or reseller for WEEE information.
VCCI statements

MSE 8321 (ISDN blade)
information
Your ISDN connection
 |
To reduce the risk of fire, use only 26 AWG or larger telecommunication line cord. |
Outside North America
Check with your network provider to ensure that your incoming ISDN PRI line is terminated in an NTU/CSU (Network Termination Unit/ Channel Service Unit). If it is not, then seek their advice regarding the provisioning of such a device. Do not connect the ISDN gateway directly to an external ISDN line.
Within North America
If your network provider has not terminated all of your incoming ISDN PRI lines with an NTU/CSU, Codian recommends that you install a suitably approved CSU to protect the ISDN gateway from damage by surges on your ISDN PRI lines.
FCC Part 68 certification
This equipment complies with Part 68 of the FCC rules and
the requirements adopted by the ACTA. On the exterior of the
cabinet of this equipment is a label that contains, among
other information, a product identifier in the format US:CODDDNANMSE8000. If
requested, this number must be provided to the telephone
company.
- ACTA Registration
Number:
CODDDNANMSE8000
- Ringer Equivalence Number (REN): N/A
- Facility Interface Code
(FIC):
04DU9.BN/DN/1KN/1SN
- Service Order Code
(SOC):
6.0F
- USOC Jack
Type:
RJ48C
A FCC compliant telephone cord and modular plug is provided
with this equipment. This equipment is designed to be
connected to the telephone network or premises wiring using a
compatible modular jack that is Part 68 compliant. See the
Getting Started Guide that accompanied the unit for
details.
The REN is used to determine the quantity of devices that
may be connected to the telephone line. Excessive RENs on the
telephone line may result in the devices not ringing in
response to an incoming call. Typically, the sum of RENs
should not exceed five (5.0). To be certain of the number of
devices that may be connected to a line (as determined by the
total RENs) contact the local telephone company.
If this equipment Codian MSE 8321 causes harm to the
telephone network, the telephone company will notify you in
advance that temporary discontinuance of service may be
required. But if advance notice isn't practical, the telephone
company will notify the customer as soon as possible. Also,
you will be advised of your right to file a complaint with the
FCC if you believe it is necessary.
The telephone company may make changes to its facilities,
equipment, operations or procedures that could affect the
operation of the equipment. If this happens the telephone
company will provide advance notice so you can make the
necessary modifications to maintain uninterrupted service.
If trouble is experienced with this equipment Codian MSE
8321 , for repair or warranty information,
contact Tandberg technical support. If the equipment is causing harm to the telephone
network, the telephone company may request that you disconnect
the equipment until the problem is resolved.
Connection to party line service is subject to state
tariffs. (Contact the state public utility commission, public
service commission or corporation commission for
information.)
MSE 8310 (ISDN blade)
information
Your ISDN connection
 |
To maintain
connectivity with the ISDN network, the ISDN GW 8310
blade must be connected to the ISDN network via an
in-building NTU (Network Termination Unit) or CSU
(Channel Service Unit). |
Check with your network provider to ensure that your
incoming ISDN PRI line has been terminated in an NTU/CSU. If
it has not, then seek their advice regarding the provisioning
of such a device. Do not connect the ISDN GW blade directly to
an external ISDN line.
 |
You must use the Y cable, even
if you plan to connect just one of the ISDN interfaces.
Using a standard straight-through cable will not
work. |
 |
The Codian ISDN GW 8310 blade
may not be compliant with EMC (Electromagnetic
Compatibility) standards if you use a cable other than
the supplied Y cable. |
FCC Part 68 certification
This equipment complies with Part 68 of the FCC rules and
the requirements adopted by the ACTA. On the exterior of the
cabinet of this equipment is a label that contains, among
other information, a product identifier in the format
US:CODXDNANMSE8000. If
requested, this number must be provided to the telephone
company.
- ACTA Registration
Number:
CODXDNANMSE8000
- Ringer Equivalence Number (REN): N/A
- Facility Interface Code
(FIC):
04DU9.BN/DN/1KN/1SN
- Service Order Code
(SOC):
6.0F
- USOC Jack
Type:
RJ48C
A FCC compliant telephone cord and modular plug is provided
with this equipment. This equipment is designed to be
connected to the telephone network or premises wiring using a
compatible modular jack that is Part 68 compliant. See the
Getting Started Guide that accompanied the unit for
details.
The REN is used to determine the quantity of devices that
may be connected to the telephone line. Excessive RENs on the
telephone line may result in the devices not ringing in
response to an incoming call. Typically, the sum of RENs
should not exceed five (5.0). To be certain of the number of
devices that may be connected to a line (as determined by the
total RENs) contact the local telephone company.
If this equipment Codian MSE 8310 causes harm to the
telephone network, the telephone company will notify you in
advance that temporary discontinuance of service may be
required. But if advance notice isn't practical, the telephone
company will notify the customer as soon as possible. Also,
you will be advised of your right to file a complaint with the
FCC if you believe it is necessary.
The telephone company may make changes to its facilities,
equipment, operations or procedures that could affect the
operation of the equipment. If this happens the telephone
company will provide advance notice so you can make the
necessary modifications to maintain uninterrupted service.
If trouble is experienced with this equipment Codian MSE
8310, for repair or warranty information,
contact Tandberg technical support. If the equipment is causing harm to the telephone
network, the telephone company may request that you disconnect
the equipment until the problem is resolved.
Connection to party line service is subject to state
tariffs. (Contact the state public utility commission, public
service commission or corporation commission for
information.)
|